This cable is used for fixed installation in low-voltage power distribution systems where enhanced mechanical protection is required. It is suitable for indoor and outdoor installations, including dry and wet locations.
With galvanised steel wire armour, the cable can be installed directly in the ground, in cable trenches, ducts, or embedded in concrete.
1. Conductor: Plain Annealed Copper, Class 2, Stranded Circular, Compacted or Sectored
2. Insulation: Cross-linked Polyethylene (XLPE) Compound
3. Filler: Non-hygroscopic material
4. Binder Tape: Non-hygroscopic material tape
5. Inner Sheath (Bedding): Polyvinyl Chloride (PVC) Compound
6. Armour: Galvanised Steel Wire Armour (SWA)
7. Binder Tape: Non-hygroscopic material tape
8. Outer Sheath: Polyvinyl Chloride (PVC) Compound
Rated Voltage (Uo/U): 600/1000 V
Operating Temperature: -15 °C to 90 °C
Final Short-Circuit Temperature: 250 °C
Test Voltage: 3.5 kV for 5 minutes
Design Specification: IEC 60502-1
Conductor: IEC 60228, BS EN 60228
Flame Retardancy: IEC 60332-1, BS EN 60332-1
Minimum Bending Radius: 8 × overall cable diameter
Maximum Pulling Tension: 70 N/mm²