This cable is used as a main power feeder in low-voltage distribution networks. It is suitable for installation in indoor and outdoor environments, including ducts and wet locations.
With aluminium wire armour providing enhanced mechanical protection, the cable is also suitable for direct burial applications where additional mechanical strength is required.
1. Conductor: Plain Annealed Copper, Class 2, Stranded Circular or Compacted
2. Insulation: Cross-linked Polyethylene (XLPE)
3. Inner Sheath: Polyvinyl Chloride (PVC) Compound
4. Armour: Aluminium Wire Armour (AWA)
5. Binder Tape: Non-hygroscopic material tape
6. Outer Sheath: Polyvinyl Chloride (PVC) Compound
7. Outer Sheath Colour: Black
Rated Voltage (Uo/U): 600/1000 V
Operating Temperature: -15 °C to 90 °C
Final Short-Circuit Temperature: 250 °C
Test Voltage: 3.5 kV for 5 minutes
Design Specification: IEC 60502-1
Conductor: IEC 60228
Flame Retardancy: IEC 60332-1
Minimum Bending Radius: 8 × overall cable diameter
Maximum Pulling Tension: 50 N/mm²

+86-510-87207972