This cable is used for fixed installation in low-voltage power distribution syst......
+ VIEW MOREIndustry News
Content
Protective conductors are essential components of electrical safety systems. Their purpose is to provide a suitable fault-current path and support the automatic disconnection of supply when an earth fault occurs.
Under IEC terminology, these conductors are commonly referred to as protective conductors (PE). In installations governed by the US National Electrical Code (NEC), the corresponding term is generally equipment grounding conductor (EGC).
Unlike phase conductors, PE conductors and EGCs are not intended to carry normal load current. Their sizing must therefore not be based solely on the continuous current-carrying capacity, or ampacity, used for phase conductors.
The applicable sizing method depends on the electrical installation standard.
This guide explains protective conductor sizing under IEC 60364-5-54, followed by a comparison with NEC 250.122 for North American projects.
A protective conductor is provided for electrical safety, including the connection of exposed-conductive-parts to the protective earthing arrangement.
During an earth fault, the protective conductor may form part of the fault-current path, allowing the protective device to disconnect the affected circuit within the required time.
Its performance depends on several factors:
Conductor material and cross-sectional area.
Prospective earth-fault current.
Fault duration.
Protective device characteristics.
Fault-loop impedance.
Earthing arrangement.
Mechanical protection and installation conditions.
A protective conductor must be capable of withstanding the thermal and mechanical effects associated with the relevant fault conditions.
It must also form part of an earthing and protective arrangement that satisfies the applicable automatic disconnection requirements.
Important: PE conductors, neutral conductors and combined protective and neutral conductors (PEN) perform different functions and must not be treated as interchangeable.
IEC 60364-5-54 provides requirements for earthing arrangements, protective conductors and protective bonding conductors in low-voltage electrical installations.
For protective conductor cross-sectional area, IEC 60364-5-54 permits two principal approaches:
Selection using the simplified sizing table.
Calculation based on short-circuit thermal withstand.
Both approaches remain subject to the applicable minimum cross-sectional area, installation and protective requirements.
Where a project evaluates both methods, the designer may select the larger resulting conductor size as a conservative design choice. This should not be confused with a universal IEC requirement to calculate both values and always adopt the larger one.
For protective conductors made of the same material as the corresponding line conductors, the simplified relationship is:
| Cross-sectional Area of Line Conductor, S | Minimum Protective Conductor Area |
|---|---|
| S ≤ 16 mm² | S |
| 16 mm² < S ≤ 35 mm² | 16 mm² |
| S > 35 mm² | S / 2 |
Example 1:
A circuit uses a 10 mm² copper line conductor.
Under the simplified table, the corresponding copper PE conductor is 10 mm².
Example 2:
A circuit uses a 25 mm² copper line conductor.
Under the simplified table, the corresponding copper PE conductor is 16 mm².
Example 3:
A circuit uses a 70 mm² copper line conductor.
Under the simplified table, the calculated copper PE area is:
70 / 2 = 35 mm²
The selected conductor must satisfy the applicable minimum requirement and use an appropriate available conductor size.
The simplified table above applies where the protective conductor and line conductor are made of the same material.
Where different materials are used, such as an aluminium line conductor with a copper protective conductor, the applicable material correction provisions of IEC 60364-5-54 must be considered.
The table should not be applied directly to dissimilar conductor materials without the required adjustment.
Where a protective conductor is not incorporated in a cable and is not enclosed in a common enclosure with the line conductors, additional minimum cross-sectional area requirements apply.
For the relevant IEC installation conditions, the following minimum sizes are commonly applicable:
| Protective Conductor Material | Mechanically Protected | Not Mechanically Protected |
|---|---|---|
| Copper | 2.5 mm² | 4 mm² |
| Aluminium | 16 mm² | 16 mm² |
These are minimum requirements for the specified installation arrangements.
They do not replace the need to determine the protective conductor size required by the circuit design.
A protective conductor may need to be larger because of the selected sizing method, fault conditions or other applicable requirements.
A PEN conductor combines protective and neutral functions.
Under the relevant IEC requirements, minimum PEN conductor cross-sectional areas are generally:
10 mm² copper.
16 mm² aluminium.
PEN conductors are subject to additional restrictions concerning the earthing arrangement, installation and conductor construction.
A normal PE conductor should not be described or specified as a PEN conductor unless the combined function is explicitly required and permitted.
IEC 60364-5-54 also provides a calculation-based method for determining the protective conductor cross-sectional area from short-circuit thermal withstand.
For applicable fault-clearing times not exceeding 5 seconds, the simplified adiabatic relationship is:
S_PE ≥ I × √t / k
Where:
| Symbol | Meaning | Unit |
|---|---|---|
| S_PE | Required protective conductor cross-sectional area | mm² |
| I | Relevant prospective fault current, RMS | A |
| t | Fault-clearing time | s |
| k | Factor determined by conductor material, insulation and applicable temperature limits | A·√s/mm² |
The k factor must be selected for the actual protective conductor construction and applicable initial and final temperatures.
The following values are commonly used for the stated insulated conductor conditions:
| Conductor Material | Insulation | Typical k Value |
|---|---|---|
| Copper | PVC | 115 |
| Copper | XLPE or EPR | 143 |
| Aluminium | PVC | 76 |
| Aluminium | XLPE or EPR | 94 |
Important: These are not universal values for every protective conductor. The applicable k factor must be verified against the relevant IEC provisions and actual conductor conditions.
Assume a copper protective conductor with XLPE insulation is subject to:
Prospective earth-fault current: 5,000 A.
Fault-clearing time: 0.2 s.
Applicable k factor: 143.
The required cross-sectional area is:
S_PE ≥ 5,000 × √0.2 / 143
S_PE ≥ 15.64 mm²
A 16 mm² copper conductor would satisfy this illustrative thermal calculation.
However, the final conductor selection must also satisfy the other applicable installation and protective requirements.
The example is not a complete verification of an electrical installation.
The thermal stress experienced by a protective conductor depends on both fault current and fault duration.
A higher fault current does not necessarily require a larger conductor if the protective device clears the fault sufficiently quickly.
Conversely, a lower fault current sustained for a longer duration may produce substantial thermal stress.
The designer must use the relevant protective device operating characteristics and prospective fault conditions rather than assume a fixed clearing time for every circuit.
For projects governed by the US National Electrical Code, equipment grounding conductors are generally sized according to NEC Article 250.
NEC 250.122 establishes minimum sizing requirements for equipment grounding conductors based primarily on the rating or setting of the overcurrent protective device protecting the circuit.
This differs from the simplified IEC approach, which relates protective conductor size to the line conductor cross-sectional area.
The following table provides selected reference values for wire-type equipment grounding conductors.
| Rating or Setting of Overcurrent Device, Not Exceeding | Copper EGC | Aluminium or Copper-clad Aluminium EGC |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
| 400 A | 3 AWG | 1 AWG |
| 600 A | 1 AWG | 2/0 AWG |
| 1,000 A | 2/0 AWG | 4/0 AWG |
| 2,000 A | 250 kcmil | 400 kcmil |
Note: This is a condensed reference table, not a reproduction of every NEC requirement. The adopted NEC edition, applicable exceptions and local authority requirements must be checked for an actual project.
Under NEC 250.122(B), when ungrounded conductors are increased in size under circumstances covered by that provision, wire-type equipment grounding conductors generally must also be increased proportionately by circular-mil area, subject to applicable exceptions.
Voltage-drop control is a common reason for increasing line conductor size.
However, the rule should not be described as applying only to voltage-drop-related increases.
Parallel conductor installations may require equipment grounding conductors in each raceway or other permitted wiring arrangement.
The applicable NEC provisions must be followed when determining the number, location and size of the EGCs.
The required EGC area should not simply be divided by the number of parallel raceways without checking the relevant NEC requirements.
IEC and NEC use different terminology, conductor sizing methods and standard conductor size systems.
| Item | IEC 60364-5-54 | NEC 250.122 |
|---|---|---|
| Common term | Protective conductor (PE) | Equipment grounding conductor (EGC) |
| Primary sizing approach | Simplified table or thermal calculation | Minimum sizing based primarily on upstream overcurrent protective device |
| Common conductor size unit | mm² | AWG or kcmil |
| Main reference | IEC 60364-5-54 | NFPA 70 / NEC Article 250 |
| Additional considerations | Material, fault conditions, installation and protection requirements | Applicable sizing adjustments, wiring method and code exceptions |
| Typical use | IEC-governed LV installations | NEC-governed electrical installations |
No.
A conductor size selected under IEC 60364-5-54 cannot automatically be declared compliant with NEC 250.122 merely by converting mm² into AWG.
Likewise, an EGC selected from NEC Table 250.122 cannot automatically be treated as an IEC-compliant PE conductor.
For international projects, the governing electrical installation standard should be established before conductor sizing is finalised.
Where project specifications contain requirements from more than one standard system, the design engineer should resolve the applicable requirements and any conflicts before approving the cable construction.
For low-voltage power cables, the protective conductor may be provided as:
An insulated core within a multicore cable.
A separate insulated protective conductor.
Another permitted conductive arrangement satisfying the applicable installation standard.
For example, a low-voltage multicore cable may be specified with three phase conductors and a separate protective conductor core.
The required PE conductor cross-sectional area should be established by the electrical designer according to the governing installation standard.
Cable manufacturers should not assume that every four-core cable is suitable for a three-phase circuit with a PE conductor.
A fourth core may instead be intended as a neutral conductor.
The required function of each core must be clearly identified in the cable specification.
The simplified IEC PE sizing table discussed above is intended for low-voltage electrical installations within the scope of IEC 60364.
Medium-voltage cable systems require additional consideration of:
Metallic screen construction.
Screen cross-sectional area.
Armour bonding.
Prospective earth-fault current.
Fault duration.
Earthing arrangement.
Joint and termination design.
Applicable utility and project specifications.
Where relevant, IEC 61936-1 and other applicable standards should be considered for the overall electrical installation.
A medium-voltage cable may include a copper wire screen, copper tape screen, metallic sheath or armour.
These components do not necessarily perform the same electrical or mechanical function.
Their suitability for carrying earth-fault current depends on their construction, continuity, bonding arrangement and verified fault withstand capability.
A cable's metallic screen or armour should therefore not be sized solely by applying the simplified low-voltage PE sizing table.
The required metallic screen construction and short-circuit withstand should be confirmed against the purchaser's technical specification.
For cable manufacturers, a complete technical enquiry helps ensure that the proposed construction matches the electrical design.
Buyers should provide the following information where applicable:
| Item | Required Information |
|---|---|
| Rated voltage | For example, 0.6/1 kV or the applicable MV rating |
| Applicable standard | IEC, NEC-governed project specification, or other required standard |
| Line conductor material | Copper or aluminium |
| Line conductor size | Cross-sectional area in mm² or applicable AWG/kcmil size |
| Number of cores | Including identification of phase, neutral and PE functions |
| PE conductor material | Copper or aluminium, where permitted |
| PE conductor size | Required cross-sectional area |
| Insulation | XLPE, PVC or other specified material |
| Outer sheath | PVC, PE, LSZH or other specified material |
| Armour | SWA, STA, AWA or unarmoured |
| Installation method | Cable tray, duct, direct burial or other arrangement |
| Fault requirements | Prospective fault current and clearing time, where relevant |
| Additional requirements | Flame retardance, fire resistance, moisture protection or other specified performance |
For medium-voltage cables, the enquiry should also identify the required metallic screen construction and fault-current withstand requirements.
If the PE or screen cross-sectional area has not yet been determined, the buyer should provide the relevant design information for technical clarification.
Protective conductor sizing is an electrical safety requirement and should not be treated as an ordinary cable ampacity calculation.
Under IEC 60364-5-54, the protective conductor cross-sectional area may be determined using the applicable simplified sizing table or a calculation based on short-circuit thermal withstand.
Under NEC 250.122, wire-type equipment grounding conductor sizing is based primarily on the upstream overcurrent protective device, together with the applicable adjustment and installation requirements.
For both systems, the final conductor selection must support the required protective function under the actual installation and fault conditions.
In medium-voltage cable systems, metallic screens, armour and associated bonding arrangements require separate technical consideration.
The final cable specification should be confirmed against the governing standard, approved electrical design and manufacturer's published technical data.
Xinyu Cable manufactures low- and medium-voltage power cables for utility distribution, industrial facilities, infrastructure and renewable energy projects.
Our product range includes copper and aluminium conductor power cables, XLPE-insulated cables, multicore low-voltage cables, and armoured and unarmoured cable constructions.
For project enquiries, customers can provide their required conductor sizes, core configurations, protective conductor requirements, metallic screen specifications and applicable technical standards.
Our team can review the requested cable construction and provide relevant product information and quotations.
Send us your technical specification, cable schedule or bill of quantities (BOQ).
This cable is used for fixed installation in low-voltage power distribution syst......
+ VIEW MORE
This multi-core XLPE insulated PVC sheathed cable is designed for low-voltage ne......
+ VIEW MORE
This 8.7/15(17.5)kV medium voltage power cable is designed with compacted copper......
+ VIEW MORE
This 8.7/15kV multi-core power cable is constructed with compacted copper conduc......
+ VIEW MORE
This 8.7/15kV multi-core power cable adopts a layered design based on compacted ......
+ VIEW MORE
This 8.7/15(17.5)kV XLPE insulated unarmored power cable is developed for medium......
+ VIEW MORE
Ready To Customise
Your Cable Products?
